Ampérage: 54 Ampères
Tension: 600 V
Série: SMC Plus
INSPECTION GRATUITE POUR LES DÉMARREURS PROGRESSIFS EN BAS DE 100 HP.

150-A54NCD Allen Bradley
Numéro de pièce du fabricant :
123-456-789
Manufacturer part number :
150-A54NCD
150-A54NCD Allen Bradley
50 HP, Serial SMC Plus
The SMC-2™ Controller is a compact, multi-functional, versatile solidstate controller used in starting standard three-phase squirrel-cage induction motors. Three standard modes of operation are available within a single controller:
- Soft Start
- Current Limit Start
- Full Voltage Start
- Optional Soft Stop (Requires Interface Module)
The SMC-2™ Controller is available in eight sizes: 5, 9, 16, 24, 35, 54, 68, and 97 A. It is offered in three voltage ranges: 200…230V, 380…460V, and 500…575V, 50/60 Hz. The SMC-2™ Controller can be used in two configurations: as a series controller and as a motor controller with an interface option
Error codes
Power Loss
Power loss indicates that an input power phase is not present. The controller’s LCD display will identify the missing phase.
Note: If all three phases are absent when a start command is issued, the LCD will display “Starting” without motor rotation.
Line Fault ¬
Line fault with the affected phase displayed identifies three possible pre-start conditions.
• Phase loss
• Load loss
• Shorted SCR
Line fault with no phase indication is displayed when one of the following conditions occurs while the SMC Dialog Plus controller is in the run mode.
• Phase loss
• Load loss
• Shorted SCR
Overvoltage and Undervoltage Protection ¬
Overvoltage and undervoltage protection are user-defined as a percentage of the programmed line voltage. The SMC Dialog Plus controller continuously monitors the three supply phases. The calculated average is then compared to the programmed trip level.
Voltage Unbalance ¬
Voltage unbalance is detected by monitoring the three phase supply voltages. The formula used to calculate the percentage voltage unbalance is as follows:
Vu = 100 (Vd / Va)
Vu: Percent voltage unbalance
Vd: Maximum voltage deviation from the average voltage
Va: Average voltage
The controller will shut down when the calculated voltage unbalance reaches the user-programmed trip percentages.
Jam Detection
Jam detection operates when the SMC Dialog Plus controller status is “at speed.” The controller will shut down when the motor current reaches the user-defined trip level, which is based on a percentage of the programmed motor full load current rating.
Overload Protection
Overload protection is enabled in the Calibration group by programming the:
• Overload class
• Overload reset
• Motor FLC
• Service factor
Refer to Chapter 5 for more information on calibration.
Underload
Underload protection is available for undercurrent monitoring. The controller will shut down when the motor current drops below the trip level. This trip level, a percentage of the motor’s full load current rating, can be programmed.