Ampérage: 1000 Ampères
Tension:
De 900 à 1000 HP à 575V
De 700 à 800 HP à 460V
350 HP à 240V
Série:MS6
INSPECTION GRATUITE POUR CE DÉMARREUR PROGRESSIF
MS6-1000 (Standard Unit) Saf
Numéro de pièce du fabricant :
123-456-789
Manufacturer part number :
MS6-1000 (Standard Unit)
MS6-1000 (Standard Unit) Saf
Serial MS6
Error codes
Code 1501 Fault name : Shear Pin Fault
Description : Enables and disables the shear pin fault.
The shear pin fault is automatically disabled during jog.
Code 1502 Fault name : MOL Fault
Description : Sets up the class of overload that will be used.
Can also disable the overload.
Code 1503 Fault name : Overload Level
Description : Represents has a percentage the amount of overload that has accumulated.
Once this level reaches 100% the Opal will trop on a MOL FLT
This level will increase based on the class set in parameter 1502 any time that the current feedback is above the name place current (parameter 1301) multiplied by the service factor (parameter 1303).
This level will decrease any time that the current feedback is below that level.
If this level reaches 100% and the drive trips, a reset will not be allowed until this level has decreased to 15%.
Code 1504 Fault name : Comm Fault Time
Description : This is the time used to determine a communication fault.