top of page

SSW-06.0010 WEG

Amperage: 6.5 Amps Voltage: 7.5 HP at 575V 5 HP at 460V 5 HP at 400V 3 HP at 240V Serial: SSW-06 FREE INSPECTION FOR SOFTSTARTS UNDER 100 HP.

Numéro de pièce du fabricant : 

123-456-789

Manufacturer part number : 

SSW-06.0010

Détails

SSW-06.0010 WEG


7.5 HP at 575V, Serial SSW-06

 


Error codes

 

 

 

 

Code 1501   Fault name : Shear Pin Fault

                   Description : Enables and disables the shear pin fault.

                                      The shear pin fault is automatically disabled during jog.

 

Code 1502   Fault name : MOL Fault

                   Description : Sets up the class of overload that will be used.

                                      Can also disable the overload.

 

Code 1503   Fault name : Overload Level

                   Description : Represents has a percentage the amount of overload that has accumulated.

                                      Once this level reaches 100% the Opal will trop on a MOL FLT

                                       This level will increase based on the class set in parameter 1502 any time that the current feedback is above the name place current (parameter 1301) multiplied by the service factor (parameter 1303).

                                       This level will decrease any time that the current feedback is below that level.

                                       If this level reaches 100% and the drive trips, a reset will not be allowed until this level has decreased to 15%.

                                               

Code 1504     Fault name : Comm Fault Time

                     Description : This is the time used to determine a communication fault.

 

 

 

 

 